Entry thread Pg
Thread Pg 11 Pg 11 Pg 16 Pg 16 Pg 21 Pg 21 Pg 29 Pg 29
Min. clamping range 8 mm 11 mm 11 mm 16 mm 16 mm 21 mm 21 mm 28.5 mm
Max. clamping range 10.5 mm 15 mm 15 mm 20.5 mm 20.5 mm 25.5 mm 25.5 mm 33 mm
Clamping range with inlet min. 6 mm 8 mm 8 mm 12.5 mm 12.5 mm 17 mm 17 mm 24 mm
Clamping range with inlet max. 8 mm 11 mm 11 mm 16 mm 16 mm 21 mm 21 mm 28.5 mm
Spanner size 21/18 mm 24 mm 24 mm 30 mm 30 mm 36 mm 38/36 mm 46 mm
Properties For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances
Thread type Pg Pg Pg Pg Pg Pg Pg Pg
clamp technology Compression technology Compression technology Compression technology Compression technology Compression technology Compression technology Compression technology Compression technology
Contact collet collet collet collet collet collet collet collet
Protection class IP69, IP68 IP69, IP68 IP69, IP68 IP69, IP68 IP69, IP68 IP69, IP68 IP69, IP68 IP69, IP68
Protection class with condition IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69 IP 68 (10 bar) / IP69
Shielded design (EMC) Yes Yes Yes Yes Yes Yes Yes Yes
Artikel-No. 1000.11.85.080 1000.11.85.120 1000.16.85.120 1000.16.85.150 1000.21.85.160 1000.21.85.190 1000.29.85.220 1000.29.85.250
E-Number
Packaging / Shipping - / 25 - / 25 - / 25 - / 25 - / 20 - / 25 - / 20 - / 5
Available with sealing inserts conformity with EN 45545 / NFPA 130. When placing an inquiry, prefix the article number by the capital F. Important: To provide the best possible protection for the cable shield and the cable, it is necessary to install a copper EMC tape. Further dimensions upon request

Mounting instruction for copper tape

Progress® EMC Serie 85
Progress® EMC Serie 85
To provide the best possible protection for
the cable shield, it is necessary to install
a copper EMC tape (copper adhesive tape
25 mm wide, Scotch 3M type 1181).
To provide the best possible protection for the cable shield, it is necessary to install a copper EMC tape (copper adhesive tape 25 mm wide, Scotch 3M type 1181).
Information Table for Optimum shield contact. The information is provided as a work instruction and facilitates professional installation of the Progress EMC Series 85 cable gland. The reference values are
non-binding.
Information Table for Optimum shield contact. The information is provided as a work instruction and facilitates professional installation of the Progress EMC Series 85 cable gland. The reference values are non-binding.

Dimensions / Form

Thread:
Pg 11
Spanner size:
24 mm
Dimension H:
47 mm
Dimension X:
20 mm
Thread length L:
8 mm

Connections / Entries

Min. clamping range:
11 mm
Max. clamping range:
15 mm
Clamping range with inlet min.:
8 mm
Clamping range with inlet max.:
11 mm
clamp technology:
Compression technology
Contact:
collet

Safety / Properties

Shielded design (EMC):
Yes

Features

Properties:
For high leakage currents, concentric shield contact with minimal transfer resistances and transfer impedances
Thread type:
Pg

Approvals / Certifications

Protection class:
IP68, IP69
Protection class with condition:
IP 68 (10 bar) / IP69

Storage / Installation / Operation

Minimum operating temperature:
-40 °C
Maximum operating temperature:
100 °C
Instruction

Assembly instructions cable glands Progress® EMC Series 85

115.1 KB | 04/11/2025